Asli Tipe C C120H 3P 80A 100A 125A 400V 50/60Hz Distribusi Daya Perlindungan Mikro Tinggi-Break Circuit Breaker
main information |
Product Series |
Acti 9 |
Product Series |
Acti 9 |
product name |
C120 |
product type |
Miniature Circuit Breaker |
Product short name |
C120L |
Number of poles |
3P |
Applications |
Distribution protection |
Number of protection poles |
3 |
Rated current [In] |
80 A at 30 ° C |
Network Type |
AC |
Release type |
Thermal magnetic |
Trip curve |
C |
Breaking capacity |
10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 |
30 kA Icu at 230 ... 240 V AC 50/60 Hz conforming to IEC 60947-2 |
15 kA Icu at 400 ... 415 V AC 50/60 Hz conforming to IEC 60947-2 |
15000 A Icn at 400 V AC 50/60 Hz conforming to IEC 60898-1 |
Isolation function |
Applicable to IEC 60947-2 |
Additional information |
Network frequency |
50/60 Hz |
Rated operating voltage [Ue] |
400 V AC 50/60 Hz |
Magnetic trip limit |
5 ... 10 x In |
Current limit level |
3 conforming to IEC 60898-1 |
Rated insulation voltage [Ui] |
500 V AC 50/60 Hz conforming to IEC 60947-2 |
Rated impulse withstand voltage [Uimp] |
6 kV conforming to IEC 60947-2 |
Contact position indication |
Have |
Control type |
handle |
Local signal indication |
On / off indication |
Installation type |
Locking clip lock |
Installation method |
DIN rail mounting |
Width (a multiple of 9mm) |
9 |
height |
86 mm |
width |
81 mm |
depth |
73 mm |
product weight |
615 g |
Mechanical life |
20000 times |
Electrical life |
5000 times |
Wiring capacity |
Tunnel-type terminal upper or lower wiring 1… 50 mm² Single-stranded hard wire without |
cymbal terminal |
Stripping length |
Power circuit: 14 mm |
Tightening torque |
Power circuit: 3.5 Nm |
Leakage current protection |
(Required) Additional assembly |
surroundings |
Standards compliant |
IEC 60898-1 |
GB 10963.1 |
certified product |
CE |
CCC |
IP protection level |
IP20 according to IEC 60529 |
Pollution degree |
3 conforming to IEC 60947-2 |
Operating temperature |
-30 ... 70 ° C |
Ambient storage temperature |
-40… 80 ° C |
Model Number : A9N198*
is_customized : Yes
Rated Voltage : 400V
Type : Mini
Standard : IEC/EN60898-1 GB10963.1
Poles Number : 3